{"cve":{"cve_id":"CVE-2024-6242","is_kev":false,"kev_date_added":null,"kev_vendor_project":null,"kev_product":null,"kev_vulnerability_name":null,"kev_short_description":null,"kev_required_action":null,"kev_due_date":null,"kev_known_ransomware":null,"kev_notes":null,"kev_cwes":null,"epss_score":0.09197,"epss_percentile":0.94671,"epss_as_of":"2026-06-23","description":"A vulnerability exists in Rockwell Automation affected products that allows a threat actor to bypass the Trusted® Slot feature in a ControlLogix® controller. If exploited on any affected module in a 1756 chassis, a threat actor could potentially execute CIP commands that modify user projects and/or device configuration on a Logix controller in the chassis.","published_at":"2024-08-01T15:15:32.220000Z","last_modified_at":null,"cvss_v3_score":null,"cvss_v3_vector":null,"cvss_v3_severity":null,"cvss_v4_score":7.3,"cvss_v4_vector":"CVSS:4.0/AV:N/AC:L/AT:P/PR:L/UI:N/VC:L/VI:H/VA:H/SC:L/SI:H/SA:H","cvss_v4_severity":"HIGH","ssvc_decision":null,"ssvc_exploitation":"none","ssvc_automatable":false,"ssvc_technical_impact":"total","cwes":["CWE-420"],"nvd_references":["https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1682.html"],"vuln_status":null,"trending_score":null,"is_trending":false,"has_trended":false,"trended_number_one":false,"trending_peak_score":null,"trending_peak_rank":null,"started_trending_at":null,"trended_number_one_at":null,"summary_generated":null,"summary_generated_at":null,"summary_model":null,"created_at":"2026-06-24T00:09:39.878444Z","updated_at":"2026-06-29T02:20:07.496563Z"},"effective_severity":"HIGH","badges":[],"impact_analysis":[],"cvss_v3_decoded":{"version":null,"metrics":[]},"cvss_v4_decoded":{"version":"4.0","metrics":[{"metric":"AV","name":"Attack Vector","value":"N","value_label":"Network"},{"metric":"AC","name":"Attack Complexity","value":"L","value_label":"Low"},{"metric":"AT","name":"Attack Requirements","value":"P","value_label":"Present"},{"metric":"PR","name":"Privileges Required","value":"L","value_label":"Low"},{"metric":"UI","name":"User Interaction","value":"N","value_label":"None"},{"metric":"VC","name":"Confidentiality (Vulnerable System)","value":"L","value_label":"Low"},{"metric":"VI","name":"Integrity (Vulnerable System)","value":"H","value_label":"High"},{"metric":"VA","name":"Availability (Vulnerable System)","value":"H","value_label":"High"},{"metric":"SC","name":"Confidentiality (Subsequent System)","value":"L","value_label":"Low"},{"metric":"SI","name":"Integrity (Subsequent System)","value":"H","value_label":"High"},{"metric":"SA","name":"Availability (Subsequent System)","value":"H","value_label":"High"}]},"affected":[{"vendor_slug":"rockwell-automation","vendor_name":"Rockwell Automation","product_slug":"1756-en2f","product_name":"1756-EN2F","version_start":"v5.007(unsigned)/v5.027(signed)","version_start_inclusive":true,"version_end":"v5.007(unsigned)/v5.027(signed)","version_end_inclusive":true,"cpe23_uri":"cve5:rockwell-automation:1756-en2f:v5.007(unsigned)/v5.027(signed):v5.007(unsigned)/v5.027(signed)"},{"vendor_slug":"rockwell-automation","vendor_name":"Rockwell Automation","product_slug":"1756-en2f","product_name":"1756-EN2F","version_start":"1756-EN2F/C: V10.009","version_start_inclusive":true,"version_end":"1756-EN2F/C: V10.009","version_end_inclusive":true,"cpe23_uri":"cve5:rockwell-automation:1756-en2f:1756-EN2F/C: V10.009:1756-EN2F/C: V10.009"},{"vendor_slug":"rockwell-automation","vendor_name":"Rockwell Automation","product_slug":"1756-en2t","product_name":"1756-EN2T","version_start":"v5.007(unsigned)/v5.027(signed)","version_start_inclusive":true,"version_end":"v5.007(unsigned)/v5.027(signed)","version_end_inclusive":true,"cpe23_uri":"cve5:rockwell-automation:1756-en2t:v5.007(unsigned)/v5.027(signed):v5.007(unsigned)/v5.027(signed)"},{"vendor_slug":"rockwell-automation","vendor_name":"Rockwell Automation","product_slug":"1756-en2t","product_name":"1756-EN2T","version_start":"1756-EN2T/D: V10.006","version_start_inclusive":true,"version_end":"1756-EN2T/D: V10.006","version_end_inclusive":true,"cpe23_uri":"cve5:rockwell-automation:1756-en2t:1756-EN2T/D: V10.006:1756-EN2T/D: V10.006"},{"vendor_slug":"rockwell-automation","vendor_name":"Rockwell Automation","product_slug":"1756-en2tp","product_name":"1756-EN2TP","version_start":"1756-EN2TP/A: V10.020","version_start_inclusive":true,"version_end":"1756-EN2TP/A: V10.020","version_end_inclusive":true,"cpe23_uri":"cve5:rockwell-automation:1756-en2tp:1756-EN2TP/A: V10.020:1756-EN2TP/A: V10.020"},{"vendor_slug":"rockwell-automation","vendor_name":"Rockwell Automation","product_slug":"1756-en2tr","product_name":"1756-EN2TR","version_start":"1756-EN2TR/C: V10.007","version_start_inclusive":true,"version_end":"1756-EN2TR/C: V10.007","version_end_inclusive":true,"cpe23_uri":"cve5:rockwell-automation:1756-en2tr:1756-EN2TR/C: V10.007:1756-EN2TR/C: V10.007"},{"vendor_slug":"rockwell-automation","vendor_name":"Rockwell Automation","product_slug":"1756-en2tr","product_name":"1756-EN2TR","version_start":"v5.007(unsigned)/v5.027(signed)","version_start_inclusive":true,"version_end":"v5.007(unsigned)/v5.027(signed)","version_end_inclusive":true,"cpe23_uri":"cve5:rockwell-automation:1756-en2tr:v5.007(unsigned)/v5.027(signed):v5.007(unsigned)/v5.027(signed)"},{"vendor_slug":"rockwell-automation","vendor_name":"Rockwell Automation","product_slug":"1756-en3tr","product_name":"1756-EN3TR","version_start":"v5.007(unsigned)/v5.027(signed)","version_start_inclusive":true,"version_end":"v5.007(unsigned)/v5.027(signed)","version_end_inclusive":true,"cpe23_uri":"cve5:rockwell-automation:1756-en3tr:v5.007(unsigned)/v5.027(signed):v5.007(unsigned)/v5.027(signed)"},{"vendor_slug":"rockwell-automation","vendor_name":"Rockwell Automation","product_slug":"1756-en3tr","product_name":"1756-EN3TR","version_start":"1756-EN3TR/B: V10.007","version_start_inclusive":true,"version_end":"1756-EN3TR/B: V10.007","version_end_inclusive":true,"cpe23_uri":"cve5:rockwell-automation:1756-en3tr:1756-EN3TR/B: V10.007:1756-EN3TR/B: V10.007"},{"vendor_slug":"rockwell-automation","vendor_name":"Rockwell Automation","product_slug":"1756-en4tr","product_name":"1756-EN4TR","version_start":"V2","version_start_inclusive":true,"version_end":"V2","version_end_inclusive":true,"cpe23_uri":"cve5:rockwell-automation:1756-en4tr:V2:V2"},{"vendor_slug":"rockwell-automation","vendor_name":"Rockwell Automation","product_slug":"controllogix-5580-1756-l8z","product_name":"ControlLogix® 5580 (1756- L8z)","version_start":"V28","version_start_inclusive":true,"version_end":"V28","version_end_inclusive":true,"cpe23_uri":"cve5:rockwell-automation:controllogix-5580-1756-l8z:V28:V28"},{"vendor_slug":"rockwell-automation","vendor_name":"Rockwell Automation","product_slug":"guardlogix-5580-1756-l8zs","product_name":"GuardLogix 5580 (1756- L8zS)","version_start":"V31","version_start_inclusive":true,"version_end":"V31","version_end_inclusive":true,"cpe23_uri":"cve5:rockwell-automation:guardlogix-5580-1756-l8zs:V31:V31"}],"exploit_refs":[],"news":[],"references":[{"url":"https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1682.html","source_type":"VENDOR_ADVISORY","tags":["advisory"]}],"timeline":[{"type":"published","at":"2024-08-01T15:15:32.220000Z","label":"CVE published","source":null},{"type":"cvss_changed","at":"2026-06-28T17:39:54.274049Z","label":"CVSS score revised","source":"cvelistv5"},{"type":"cvss_changed","at":"2026-06-28T17:39:54.274049Z","label":"CVSS score revised","source":"cvelistv5"},{"type":"cvss_changed","at":"2026-06-28T17:39:54.274049Z","label":"CVSS score revised","source":"cvelistv5"},{"type":"ssvc_changed","at":"2026-06-29T02:20:07.496563Z","label":"SSVC decision revised","source":"vulnrichment"},{"type":"ssvc_changed","at":"2026-06-29T02:20:07.496563Z","label":"SSVC decision revised","source":"vulnrichment"},{"type":"ssvc_changed","at":"2026-06-29T02:20:07.496563Z","label":"SSVC decision revised","source":"vulnrichment"}]}